Troubleshoot the Module
Status Indicators
The module uses the status indicators shown below.
Topic
Page
Indicator
Status
Description
OK Status
Steady green
The module is broadcasting inputs in a normal operating state.
Flashing green
The module has passed internal diagnostics, but is not broadcasting
inputs because a valid connection is not established, the controller is
in Program mode, or the module is inhibited.
Uninhibit the connection, transition the controller to Run mode, or
establish a connection to enable communication to the module.
Steady red
The module must be replaced.
Flashing red
Previously established communication has timed out.
Check the controller and chassis communication.
Standard Hardware
Input Status
Yellow
The hardware input is On.
Counter Input Status
Yellow
The counter input is On.