Chapter 5

Troubleshoot the Module

Module Error Codes

In RSLogix 5000 software, errors appear in the Module Fault area on the
Connection tab of the Module Properties dialog box (

Figure 19

). The table

below lists possible errors.

Error Code

Description

0x100

Connection in Use—Typically occurs when the module detects a connection attempt, but never
receives data resulting in a 60 second timeout. This scenario can be caused by an error with the
communication module.

0x106

Ownership Conflict—The controller-to-module connection is already in use by another
controller. Only one controller can own the connection to the counter module. All other controllers
must use a Listen-only connection.

0x108

Invalid Connection Type—The module’s owner-controller is not using multicast communication,
so the module cannot establish a Listen-only multicast connection.

0x111

RPI Not Supported—The RPI is not within a valid range of 200 μs…750 ms.

0x114

Product Code Mismatch—Electronic keying error. The module catalog number, such as
1756-LSC8XIB8I, in the I/O Configuration tree does not match the catalog number of the
corresponding physical module. For more information about electronic keying, see

Appendix A

.

0x115

Product Type Mismatch—Electronic keying error. The module product type, such as Multi-
channel Digital, in the I/O Configuration tree does not match the product type of the corresponding
physical module. For more information about electronic keying, see

Appendix A

.

0x116

Revision Mismatch—Electronic keying error. The cause of the error depends on which electronic
keying option is specified on the General tab of the Module Properties dialog box:

If the Compatible Keying option is specified, the module revision number is incompatible with

the revision number of the corresponding physical module.

If the Exact Match option is specified, the module revision number is not an exact match with the

revision number of the corresponding physical module.

For more information about electronic keying, see

Appendix A

.

0x119

Controlling Connection Not Open—The module cannot establish a Listen-only connection
because there is currently no connection with the owner-controller.

0x02

Resources Unavailable—The module cannot establish a connection due to lack of resources.

0x25

Key Failure—The physical module does not match the electronic keying information.
For more information about electronic keying, see

Appendix A

.