Alternate Wiring for Non-IEC Type 3 Sensors

The following sections provide recommendations on how to use your counter
module with an open collector sensor that is not IEC compliant.

Module Input Circuit

Refer to the input circuit shown below to wire a counter module to an open
collector sensor that requires an external pull-up resistor.

Input Specifications

Refer to the module’s input specifications in

Table 8

to choose an appropriate a

pull-up resistor as described on

page 78

.

Topic

Page

Module Input Circuit

77

Input Specifications

77

Choose a Pull-up Resistor for an Open Collector Sensor

78

Open Collector Wiring without a Resistor

78

V_Supply

R_Pullup

IN-x or CTR-x

Current

Limit

HiSpeed Logic

Opto Coupler

GND-x or CTR GND-x

Module

Display

Table 8 - Counter Module without External Resistor

Voltage across Terminals

Input Current @ 25 °C (77 °F)

Off ≤

5V

(1)

(1) 5V or less across the input terminals for a module Off state.

< 1.5 mA

Turn-on at 8.9V

2.5 mA

10V

(2)

(2) 10V minimum required across input terminals for a module On state.

3.8 mA

24V

4.8 mA

30V

5.0 mA