Nru conceptual schematic, Figure 1.1, Nru conceptual schematic -5 – Rockwell Automation 2364E Non-Regenerative DC Bus Supply Unit (NRU) User Manual

Page 19

Advertising
background image

Publication 2364E-5.01 April 2002

Overview

1-5

NRU Conceptual Schematic

Customer-supplied, 3-phase AC power is supplied to the system as
shown on the left side of the NRU schematic shown in Figure 1.1.
All three phases are fused and then connected to the diode-bridge
rectifier, as shown. The diode-bridge rectifier is also connected
through DC bus chokes to the DC bus.

Two of the three AC input phases are routed through primary control
transformer fusing to the control transformer. The secondary of the
control transformer, which supplies the NRU control power, can be
connected to the control bus after fusing if the control transformer is
sized accordingly. The bridge fan is connected to the NRU control
power.

Figure 1.1
Conceptual Schematic of the NRU

M

D C

B u s

Bus
Voltage
Light

(Optional Air-Flow

Sensor)

DC +
Choke

DC -
Choke

+

-

Diode Bridge

Control

Transformer

Fuses

Circuit
Breaker
or MCP

3-Phase AC
Incoming
Power

L

L

N

N

115V AC

NRU Control

Power

To Optional

115V AC

Control Bus

Bridge

Fan

Motor

(This fuse included in control

power source upgrade options)

N R U