Recommended disconnect trip settings, Table d: recommended disconnect trip settings, Figure 6 – Rockwell Automation 2364E Non-Regenerative DC Bus Supply Unit (NRU) User Manual

Page 85: Figure 7

Advertising
background image

Publication 2364E-5.01 April 2002

NRU Details

C-5

Recommended Disconnect Trip
Settings

Table D: Recommended Disconnect Trip Settings

Figure 6
180 and 350A DC NRU Recommended Motor Circuit Protector Settings

Figure 7
900A DC NRU Recommended Circuit Breaker Settings

DC Bus Current

(A DC)

NRU Current

Code

Disconnect Description

Recommended Setting(s)
shown in:

180

A

Motor Circuit Protector: 250A,
J-frame

Figure 6

350

B

Motor Circuit Protector: 400A,
K-frame

Figure 6

900

C

Circuit Breaker: 1200A
R-frame with 1200A plug

Figure 7

1500

D

Circuit Breaker: 2000A
R-frame with 1600A plug

Figure 8

2000

E

Circuit Breaker: 2000A
R-frame with 2000A plug

Figure 8

2500

F

Circuit Breaker: 3000A
SPB-frame with 2500A plug

Figure 9

3000

G

Circuit Breaker: 3000A
SPB-frame with 3000A plug

Figure 9