Recommended disconnect trip settings, Table d: recommended disconnect trip settings, Figure 6 – Rockwell Automation 2364E Non-Regenerative DC Bus Supply Unit (NRU) User Manual
Page 85: Figure 7

Publication 2364E-5.01 April 2002
NRU Details
C-5
Recommended Disconnect Trip
Settings
Table D: Recommended Disconnect Trip Settings
Figure 6
180 and 350A DC NRU Recommended Motor Circuit Protector Settings
Figure 7
900A DC NRU Recommended Circuit Breaker Settings
DC Bus Current
(A DC)
NRU Current
Code
Disconnect Description
Recommended Setting(s)
shown in:
180
A
Motor Circuit Protector: 250A,
J-frame
Figure 6
350
B
Motor Circuit Protector: 400A,
K-frame
Figure 6
900
C
Circuit Breaker: 1200A
R-frame with 1200A plug
Figure 7
1500
D
Circuit Breaker: 2000A
R-frame with 1600A plug
Figure 8
2000
E
Circuit Breaker: 2000A
R-frame with 2000A plug
Figure 8
2500
F
Circuit Breaker: 3000A
SPB-frame with 2500A plug
Figure 9
3000
G
Circuit Breaker: 3000A
SPB-frame with 3000A plug
Figure 9