Publication 2364E-5.01 April 2002

Specifications

A-5

Thru Bus Ratings per Unit

Table F: Current Ratings of DC Thru Bus

Environmental Specifications

Operating Conditions

Table G: NRU Operating Conditions

Figure 1
Altitude Derate Curve

Unit DC Bus

Current (A DC)

Thru Bus Rating

(A DC)

180

800

350

800

900

1600

1500

1600

2000

3000

2500

3000

3000

3000

Altitude

1000 meters (3,300 ft)

Ambient Temperature

0º to 40º C (32º to 104º F) ‚

Relative Humidity

5% to 95%, non-condensing

For altitudes higher than 1000 meters, derate using Figure 1.
For temperatures greater than 40º C, derate using Figure 2.

50%

60%

70%

80%

90%

100%

0 m

(0 ft)

1000 m

(3,300 ft)

2000 m

(6,600 ft)

3000 m

(9,900 ft)

4000 m

(13,200 ft)

% of NRU

Rated Amps

at 40 °C

Altitude