Thru Bus Ratings per Unit
Table F: Current Ratings of DC Thru Bus
Environmental Specifications
Operating Conditions
Table G: NRU Operating Conditions
Figure 1
Altitude Derate Curve
Unit DC Bus
Current (A DC)
Thru Bus Rating
(A DC)
180
800
350
800
900
1600
1500
1600
2000
3000
2500
3000
3000
3000
Altitude
1000 meters (3,300 ft)
Ambient Temperature
0º to 40º C (32º to 104º F) ‚
Relative Humidity
5% to 95%, non-condensing
For altitudes higher than 1000 meters, derate using Figure 1.
For temperatures greater than 40º C, derate using Figure 2.
50%
60%
70%
80%
90%
100%
0 m
(0 ft)
1000 m
(3,300 ft)
2000 m
(6,600 ft)
3000 m
(9,900 ft)
4000 m
(13,200 ft)
% of NRU
Rated Amps
at 40 °C
Altitude