Overview

1-7

Bulletin 2364E NRU –
Standard Features

Electrical System Features

A 3-phase circuit breaker / motor circuit protector rated for
65kAIC:

• 180 and 350A DC units have motor circuit protectors

• 900, 1500, 2000, 2500, and 3000A DC units have circuit

breakers

AC line, current-limiting fuses rated at 600V AC with short
circuit protection rated at 65kAIC

A six-pulse, full-wave, 3-phase-diode-bridge rectifier unit

A DC bus choke with inductance in both +/- legs

A "basic capacity" control power transformer that supplies ONLY
the NRU with single-phase, 115V AC control power

Primary and secondary control transformer fusing (excluding the
control bus fuse that is supplied with the "6P" and "6PX" control
power source upgrade options)

A "DC-Bus-Energized" pilot light that turns on when the bus
voltage is above 50V DC

Compatible with Bulletin 1336 dynamic braking (DB) chopper
units

Note: A dynamic braking chopper unit requires an additional
cabinet section.

A bridge suppressor module

Configurations available for 230, 380, 460, and 575V AC inputs
with 180, 350, 900, 1500, 2000, 2500, and 3000A DC outputs

Utilization of #16 AWG MTW (PVC insulated) rated, stranded
copper control wiring

Packaging Features

Utilization of Bulletin 2100 CENTERLINE motor control center
(MCC) packaging makes the NRU compatibility with other
Bulletin 2100 and 2300 products

Unit depth of 20"

DC bus and control bus (if selected) depth at

•11.9 inches in 180 and 350A DC (current codes A and B)

units

•16.9 inches in 900, 1500, 2000, 2500, and 3000A DC (cur-

rent codes C, D, E, F, and G) units