Checklist for troubleshooting your nru, Figure 10.1, Checklist for troubleshooting your nru -2 – Rockwell Automation 2364E Non-Regenerative DC Bus Supply Unit (NRU) User Manual

Page 62

Advertising
background image

Publication 2364E-5.01 April 2002

10-2

Troubleshooting

Checklist for Troubleshooting
Your NRU

The following table provides a checklist to help you identify the
cause of your NRU problem.

Figure 10.1
Troubleshooting Chart

Important: Refer to the system schematics, Appendix A of this

manual, and the chapter of this manual that corresponds
to your NRU for ratings.

Type of Problem

Loss of DC Bus

Power & Control

Power

Loss of DC Bus

Power Only

Loss of Control

Power Only

Fault Indication Did you check the:

3-Phase AC Incoming Power
Circuit Breaker or MCP Operation
3-Phase Fusing
Diode Bridge
DC Choke
Control Transformer Fusing
Control Transformer Secondary
Voltage and/or Secondary Fusing
Bridge Fan
Over-Temperature Switch
Phase Loss
Phase Imbalance
External Customer Interlocks
(if present)