Nru checks before power up, Nru checks before power up -5 – Rockwell Automation 2364E Non-Regenerative DC Bus Supply Unit (NRU) User Manual

Page 57

Advertising
background image

Publication 2364E-5.01 April 2002

Installing Your NRU

9-5

NRU Checks Before Power Up

1.

Verify that the NRU does not have any mechanical damage.

2.

Verify that the NRU does not have any loose wires or buswork.

3.

Using an ohmmeter or other continuity testing device, verify that
shorts do not exist between:

Note: A small short may exist between PE and TE.

!

ATTENTION: You must perform the checks
described in this section before turning power on to the
system. Failure to do so may result in personal injury
and/or equipment damage.

ATTENTION: You must not turn on the power if the
NRU fails any of the checks described in this section.
Failure to do so may result in personal injury and/or
equipment damage.

ATTENTION: You must correct all problems before
proceeding to the next step. Failure to do so may result
in personal injury and/or equipment damage.

Source 1

Source 2

Check below if no short exists

L1

L2

L1

L3

L2

L3

L1

PE

L2

PE

L3

PE

L1

TE

L2

TE

L3

TE

DC+ Bus

DC- Bus

DC+ Bus

PE

DC- Bus

PE

DC+ Bus

TE

DC- Bus

TE

PE

TE