Functional specifications, Table d: nru functional specifications – Rockwell Automation 2364E Non-Regenerative DC Bus Supply Unit (NRU) User Manual
Page 65
Advertising
![background image](/manuals/580588/65/background.png)
Publication 2364E-5.01 April 2002
A-3
Functional Specifications
Table D: NRU Functional Specifications
AC Input Frequency Tolerance
45 to 65 Hz
AC Input Voltage Tolerance
± 10%
Overload Capability
150% maximum DC bus current for 60 seconds,
200% for 10 seconds following continuous operation
Overload Duty Cycle
1 minute out of 20 minutes at rated load and
temperature
Minimum Continuous Load Requirement
33% of rated DC bus continuous current
If the total continuous DC input current of the load is less than 33% of the rate
NRU DC bus continuous current, the bus current may become discontinuous.