Ground-fault detection option, Figure 9.1, Ground-fault detection option -4 – Rockwell Automation 2364E Non-Regenerative DC Bus Supply Unit (NRU) User Manual

Page 56

Advertising
background image

Publication 2364E-5.01 April 2002

9-4

Installing Your NRU

Ground-Fault Detection Option

If the ground-fault detection metering option is supplied on your unit,
perform the following procedures.

Note: The ground-fault detection relay can be implemented only
if the power transformer has a resistive grounded-wye secondary
with a resistance of 150 to 300 ohms (1–2A of current during a
solid ground fault).

1.

Connect terminals TB2-1 and TB2-2 across the power
transformer grounding resistor, in accordance with system
schematics and transformer manufacturer specifications.

2.

Turn the set screw until the black indicator needle aligns with the
0 (zero) mark as shown in Figure 9.1.

Figure 9.1
Setting the Ground Fault Detection

Advertising