Trical schematic (table 8.a) – Rockwell Automation 2364E Non-Regenerative DC Bus Supply Unit (NRU) User Manual

Page 52

Advertising
background image

Publication 2364E-5.01 April 2002

8-4

Your 3000A DC NRU (Current Code G)

Table 8.A: 3000A DC NRU Symbol-to-Component Cross Reference

AC 3-Phase Input Voltage

Symbol

Description

Option

230V AC

380V AC

460V AC

575V AC

AM1

Ammeter monitoring L1

3000A

CB1

Circuit breaker

3000A R-frame breaker with 3000A plug

CH11

DC choke

37 uH

CH11-TG

DC choke thermoswitch

CR1

Phase-loss relay

CR2

Fault relay

CT1, CT3

Current transformer

3000:5

D1 - 6

Diodes

5000A, 1800V AC

EA1

Powermonitor II

EA2

Bus indicator PCB

EA2F1 - 2

Bus indicator PCB fuses

1A, 1000V, HVR, 1-3/32" diameter, 3" length, 500AIC

EA3

Line RC suppressor PCB

EA4

Bridge suppressor PCB

EA5 - 6

Air flow sensor PCB

F1 - 3, F1A-3A Incoming 3-phase, line fuses

1500A, 170M

F4, F6

Primary fuse for a 2 kVA control
transformer

12A, KLDR

8A, KLDR

6.25A, KLDR

5A, KLDR

Primary fuse for a 5 kVA control
transformer

30A, KLDR

17.5A, KLDR

15A, KLDR

12A, KLDR

Primary fuse for a 10 kVA control
transformer

60A, KLDR

35A, FRS

25A, KLDR

20A,KLDR

F7

NRU control power fuse

12A, KLDR

F8

Control bus fuse for a 2 kVA
control transformer

5A, KLDR

Control bus fuse for a 5 kVA
control transformer

30A, FRN

Control bus fuse for a 10 kVA
control transformer

70A, FRN

F11 - 13

Phase-loss fuses

1A, KLDR

F14 - 16

RC suppressor fuses

25A, KTKR

HS1 - 2

Bridge heatsink

MTR1

Bridge fan

1200 CFM

MTR1-C

Bridge fan capacitor

20 uF capacitor

MTR2 - 3

Door-mounted fan by choke

6.9", 340 CFM

MTR4 - 6

Door-mounted fan by CB

6.9", 340 CFM

PL1

DC-Bus-Energized pilot light

24V AC/VDC, red, 800MR

PL2

Unit-Not-Faulted pilot light

120V AC, amber, 800MR

PS1

Air flow sensor power supply

24V DC, 1.1A

PT1

Control power transformer

A 1 kVA control transformer is standard, 5 kVA and 10 kVA control
transformers are available as options. This transformer has multiple
taps to accommodate 230, 380, 460, 575V AC primary voltages.

S1 - 2

Heatsink thermoswitch

220 °F

S3

Choke thermoswitch

S5

Air flow sensor

SP1 - 3

Line-to-line MOVs

360 J, 275V AC 460 J, 320V AC 460 J, 320V AC 550 J, 385V AC

SP4

Neutral-to-ground MOV

600 J, 550V AC 760 J, 680V AC 760 J, 680V AC 760 J, 680V AC

VM1

DC bus voltmeter

750V DC

750V DC

1000V DC

1000V DC

VM2

Ground fault detector

Components marked as being options are part of NRU standard options. Not all NRUs will have these components.