Bulletin 2364e nru – standard options, Electrical system options, Bulletin 2364e nru – standard options -9 – Rockwell Automation 2364E Non-Regenerative DC Bus Supply Unit (NRU) User Manual

Page 23: Electrical system options -9

Advertising
background image

Publication 2364E-5.01 April 2002

Overview

1-9

Bulletin 2364E NRU –
Standard Options

Electrical System Options

Analog DC bus voltage metering

Analog AC input current metering (Phase A only)

Note: The bus voltmeter and/or AC input ammeter are mounted
in a special wireway meter cover that is angled for easy viewing.

AC input and output power metering (kW) using Powermonitor II
(Bulletin 1403) for NRUs powered by 3-phase, grounded-wye
secondary supplies

Powermonitor II communication module for connecting the
Powermonitor II to Remote I/O, RS-232, or RS-485 devices

A door-mounted "Unit-Not-Faulted" pilot light that monitors air
flow sensor(s), heatsink temperature sensors, phase loss relay,
and an optional remote interlock (if supplied by customer)

A door-mounted, ground-fault detection meter for NRUs
powered by 3-phase, grounded-wye secondary supplies

Standard capacity ("6P") and extra capacity ("6PX") control
power source upgrade options are available to provide 115V AC
control bus power

Note: "6P" and "6PX" options include control bus fuse and
control busbar mounted in cabinet above power bus.

An air-flow-loss switch in all Diode Power MCC sections and in
2500/3000A DC Input Power MCC sections. This option
monitors critical NRU air flows for proper CFM

A line RC suppressor module to reduce AC line transients

Note: The line RC suppressor module is recommended when the
primary voltage of the supply transformer is 2300V AC or
greater.