Electrical specifications, Table c: nru electrical specifications – Rockwell Automation 2364E Non-Regenerative DC Bus Supply Unit (NRU) User Manual
Page 64

Publication 2364E-5.01 April 2002
A-2
Electrical Specifications
Table C: NRU Electrical Specifications
Maximum
Control Transformer kVA Ratings
Nominal Input
Voltage (V AC)
Continuous
Input Current
(A AC)
Nominal DC
Bus Voltage
(V DC)
Continuous DC
Bus Current
(A DC)
NRU
Current
Code
Rated DC
Bus kW
Basic Capacity
Optional Standard
Capacity for
Control Bus
Optional Extra
Capacity for
Control Bus
230
151
310
180
A
56
1.0
2.0
5.0
230
290
310
350
B
109
1.0
2.0
5.0
230
739
310
900
C
279
1.0
2.0
5.0
230
1229
310
1500
D
465
1.0
5.0
10.0
230
1637
310
2000
E
620
1.0
5.0
10.0
230
2050
310
2500
F
775
2.0
5.0
10.0
230
2458
310
3000
G
930
2.0
5.0
10.0
380
150
510
180
A
92
1.0
2.0
5.0
380
288
510
350
B
179
1.0
2.0
5.0
380
737
510
900
C
459
1.0
2.0
5.0
380
1227
510
1500
D
765
1.0
5.0
10.0
380
1636
510
2000
E
1020
1.0
5.0
10.0
380
2047
510
2500
F
1275
2.0
5.0
10.0
380
2455
510
3000
G
1530
2.0
5.0
10.0
460
149
620
180
A
112
1.0
2.0
5.0
460
288
620
350
B
217
1.0
2.0
5.0
460
737
620
900
C
558
1.0
2.0
5.0
460
1227
620
1500
D
930
1.0
5.0
10.0
460
1635
620
2000
E
1240
1.0
5.0
10.0
460
2046
620
2500
F
1550
2.0
5.0
10.0
460
2454
620
3000
G
1860
2.0
5.0
10.0
575
149
775
180
A
140
1.0
2.0
5.0
575
288
775
350
B
271
1.0
2.0
5.0
575
737
775
900
C
698
1.0
2.0
5.0
575
1226
775
1500
D
1163
1.0
5.0
10.0
575
1635
775
2000
E
1550
1.0
5.0
10.0
575
2045
775
2500
F
1938
2.0
5.0
10.0
575
2453
775
3000
G
2325
2.0
5.0
10.0
Refer to Table D for AC input specifications.
AC line current shown is for NRU with basic capacity control transformer. Refer to Table E for AC input current if you have selected a control
power source upgrade option.
Refer to Table D for NRU overload capability.
Rated DC bus kW is the power available on the DC thru bus. This value is independent of control transformer selection. To calculate the input
kVA, use this formula:
V = Input Voltage, line to line (V AC, i.e. from column 1)
A = Input Current (A AC, i.e. from column 2)
input kVA
V A
=
⋅
( .
)
173
1000