Specifications

Electrical Specifications

Table C: NRU Electrical Specifications

Maximum

Control Transformer kVA Ratings

Nominal Input
Voltage (V AC)

Continuous

Input Current

(A AC)

Nominal DC

Bus Voltage

(V DC)

Continuous DC

Bus Current

(A DC)

NRU

Current

Code

Rated DC

Bus kW

Basic Capacity

Optional Standard

Capacity for

Control Bus

Optional Extra

Capacity for

Control Bus

230

151

310

180

A

56

1.0

2.0

5.0

230

290

310

350

B

109

1.0

2.0

5.0

230

739

310

900

C

279

1.0

2.0

5.0

230

1229

310

1500

D

465

1.0

5.0

10.0

230

1637

310

2000

E

620

1.0

5.0

10.0

230

2050

310

2500

F

775

2.0

5.0

10.0

230

2458

310

3000

G

930

2.0

5.0

10.0

380

150

510

180

A

92

1.0

2.0

5.0

380

288

510

350

B

179

1.0

2.0

5.0

380

737

510

900

C

459

1.0

2.0

5.0

380

1227

510

1500

D

765

1.0

5.0

10.0

380

1636

510

2000

E

1020

1.0

5.0

10.0

380

2047

510

2500

F

1275

2.0

5.0

10.0

380

2455

510

3000

G

1530

2.0

5.0

10.0

460

149

620

180

A

112

1.0

2.0

5.0

460

288

620

350

B

217

1.0

2.0

5.0

460

737

620

900

C

558

1.0

2.0

5.0

460

1227

620

1500

D

930

1.0

5.0

10.0

460

1635

620

2000

E

1240

1.0

5.0

10.0

460

2046

620

2500

F

1550

2.0

5.0

10.0

460

2454

620

3000

G

1860

2.0

5.0

10.0

575

149

775

180

A

140

1.0

2.0

5.0

575

288

775

350

B

271

1.0

2.0

5.0

575

737

775

900

C

698

1.0

2.0

5.0

575

1226

775

1500

D

1163

1.0

5.0

10.0

575

1635

775

2000

E

1550

1.0

5.0

10.0

575

2045

775

2500

F

1938

2.0

5.0

10.0

575

2453

775

3000

G

2325

2.0

5.0

10.0

Refer to Table D for AC input specifications.

AC line current shown is for NRU with basic capacity control transformer. Refer to Table E for AC input current if you have selected a control

power source upgrade option.

Refer to Table D for NRU overload capability.

Rated DC bus kW is the power available on the DC thru bus. This value is independent of control transformer selection. To calculate the input

kVA, use this formula:

V = Input Voltage, line to line (V AC, i.e. from column 1)
A = Input Current (A AC, i.e. from column 2)

input kVA

V A

=

( .

)

173

1000