AC Input Customer Connection
Details

The type of AC input connection depends upon the NRU current
rating.

Table C: AC Input Customer Connection Details

Figure 5
AC Input Customer Connection Bus in 900, 1500, 2000, 2500, and 3000A DC

NRUs

DC Bus Current

(A DC)

NRU Current

Code

Type of AC Input Connection

Typical AC Input Wire Sizing
(per Phase) Based on 125% of
Rated Load and 75ºC wiring

180

A

Terminals accommodating
AWG 4 through 350 kcmil.

One AWG 3/0

350

B

Terminals accommodating
AWG 3/0 through 350 kcmil.

· One AWG 500 kcmil or
· Two AWG 3/0

900

C

One bus stub per phase. See
Figure 5.

· Three AWG 350 kcmil or
· Four AWG 4/0

1500

D

Two bus stubs per phase. See
Figure 5.

· Five AWG 350 kcmil or
· Six AWG 250 kcmil

2000

E

Two bus stubs per phase. See
Figure 5.

· Five AWG 350 kcmil,
· Six AWG 250 kcmil, or
· Seven AWG 250 kcmil

2500

F

Three bus stubs per phase.
See Figure 5.

· Seven AWG 500 kcmil or
· Eight AWG 400 kcmil

3000

G

Three bus stubs per phase.
See Figure 5.

· Eight AWG 500 kcmil

0.563 Diameter
TYP

1.844

1.750

0.83

0.88

0.250