Publication 4100-UM052B-EN-P - October 2001

Installation & Hook-Up 13

Figure 2 Mounting and Grounding Diagram

Mount the AEC next to a 1394 GMC system or an S Class Compact
motion controller on a metal enclosure panel using two 1/4 -20 or M6
bolts. Refer to the Mechanical Specifications in the Overview chapter
of this manual for mounting dimensions. Figures 3 and 4 in this
chapter show where to mount the AEC.

ATTENTION

!

To avoid a shock hazard, remove all power to the
system panel before mounting the AEC.

The 1394 contains stored energy devices. To avoid the
hazard of electrical shock, verify that all voltages are
zero (0.00) before proceeding.

#10 AWG to
Ground Bus

Ground
Lug

Internal Star Washers

AEC Mounting Tab

Size 1/4 - 20 or M6
Hardware

Tapped Hole
(Minimum of 3 Threads)

Metal Panel
(Must be connected to
earth ground.)

Scrape paint off panel to insure
electrical connection between
chassis and grounded metal plate.