Setup, Chapter objectives, Setting the rotary switches – Rockwell Automation 4100 AEC Absolute Encoder Converter Installation User Manual

Page 37: Chapter

Advertising
background image

29

Publication 4100-UM052B-EN-P - October 2001

Chapter

3

Setup

Chapter Objectives

The AEC is used in conjunction with the 1394 GMC System or the S
Class Compact motion controller and SSI transducers. It is not a
stand-alone product and must be configured to work with the
hardware connected to it. This involves specific steps that are
determined by the make and model of the hardware connected to the
AEC. This manual assumes that the GML Commander v4.01 or higher
software is used.

This chapter covers :

Explanation of the Rotary switch settings

Powering the AEC

Configuring the AEC with the GML Commander software

Homing Procedure

Aligning Absolute Device

Setting the Rotary Switches

Setting the rotary switches located on the front panel, configures the
AEC.

Before you apply power to the AEC you must configure each axis to
suit the transducer connected to it. A total of four parameters per axis
must be configured. For each axis, determine the following:

1. Transducer resolution in counts/turn (this is in counts/stroke for

linear displacement transducers). Parameter 1 is set by
configuration switch “A”. The table “Configuration Switch A” lists
all the options supported by the AEC. Use this table to select the
switch setting that matches the value for your transducer.

2. Whether the transducer is a single or multi turn device.

3. Whether Grey or Binary is used for transducer data.

4. The operation mode. Locked or free running.

IMPORTANT

Configuration switch “B” is used for setting the next
three parameters. You must find the setting that meets the
combination of values for all three parameters.