Publication 4100-UM052B-EN-P - October 2001

48 Strobe Position For Applications Not Using the 1394 or Compact

Absolute Strobe Timing

This section defines the timing requirements for the two-strobe pulse
train required for absolute position updates. The AEC must receive
two strobe pulses to initiate and complete an absolute position update
transfer. These are referred to as Ts1 and Ts2 in the data transfer
protocol diagram. The following diagram and table outline the
parametric requirements for an absolute position update cycle.

Figure 18 Absolute Position Transfer Protocol

An absolute position request is an asynchronous event initiated by
the controlling hardware. The first strobe starts the absolute position
update cycle. The first strobe (Ts1) must be active for a minimum of
100ms, but for less than 1000ms to be valid. A strobe is sourcing

Absolute Position Transfer Timing

Parameter

Locked Mode

Free-Running Mode

Min

Max

Min

Max

Tabs (absolute update cycle) = (Ts1s2 + Ts2 + Ts2hpe)

3001ms

Ts1 (Strobe1 active pulse width)

100ms

1000ms

100ms

1000ms

Ts2 (Strobe2 active pulse width)

5ms

1000ms

5ms

1000ms

Ts1s2 (time from Strobe1 inactive to strobe2 active)

Ts1+Ts1hpe+2

2000ms

Ts1+Ts1hpe+2

2000ms

Tph (time from Strobe1 inactive edge to encoder state hold)

30ms

30ms

Ts1hpe (time from Strobe1 inactive to end of encoder stream)

0

25ms

0

25ms

Ts2hpe (time from Strobe2 inactive to end of encoder stream)

0

1ms

0

1ms

Tpei (*time from MSW pulse train end to incremental updating)

0

indefinite

N/A

N/A

Thold

N/A

N/A

500ms

500ms

*Operation mode dependent: Locked or Free-Running