How to Install Your Pulse Counter Module

Publication 1794ĆUM016B-EN-P - August 2002

1.4

(35.5)

.83 (21)

2.3

(58.5)

2.3

(58.5)

1.4

(35.5)

1.4

(35.5)

Inches

(Millimeters)

Drilling Dimensions for Panel/Wall Mounting of FLEX I/O

2. Drill the necessary holes for the #6 self-tapping mounting screws.

3. Mount the mounting plate (1) for the adapter module using two

#6 self-tapping screws (18 included for mounting up to 8 modules
and the adapter).

Important: Make certain that the mounting plate is properly

grounded to the panel. Refer to “Industrial Automation
Wiring and Grounding Guidelines,” publication
1770-4.1.

4. Hold the adapter (2) at a slight angle and engage the top of the

mounting plate in the indention on the rear of the adapter module.

5. Press the adapter down flush with the panel until the locking lever

locks.

6. Position the terminal base unit up against the adapter and push the

female bus connector into the adapter.

7. Secure to the wall with two #6 self-tapping screws.

8. Repeat for each remaining terminal base unit.

Note: The adapter is capable of addressing eight modules. Do not
exceed a maximum of eight terminal base units in your system.

Mounting the Pulse Counter Module on the Terminal Base Unit

The Pulse Counter module mounts on a 1794-TB3, TB3S, -TBN or
-TBNF terminal base unit.

1. Rotate the keyswitch (1) on the terminal base unit (2) clockwise

to position 1 as required for the Pulse Counter module.