5–3

How Communication Takes Place and I/O Image Table Mapping with the DeviceNet Adapter

Publication 1794ĆUM016B-EN-P - August 2002

System throughput, from Pulse Counter to backplane, is a function
of:

the configured minimum frequency sample time

the number of channels actually configured for connection to a
specific sensor (0 or 1)

You can set the minimum frequency time during module
configuration. The selection influences the sample data rate, thus
affecting system throughput.

The number of channels included in each input scan also affects
system throughput.

FLEX I/O Pulse Counter module data table mapping is shown
below.

Pulse Counter Module (1794ĆIP4) Image Table Mapping

Module Image

I/O Image

Input Size

Output Size

0 to 3 Words

1 to 10 Words

Counter 00 - 16-bit period measurement or low word of 32Ćbit period measurement for channel 0

Code for identification of software version

Control Word 0 - Sets the measure function

Control Word 2 - sets the start of a new measurement

Control Word 1 - Sets the clock frequency and period multiple

Counter 01 - pulse counter for channel 0 or high word of 32Ćbit period measurement

Counter 10 - 16-bit period measurement or low word of 32Ćbit period measurement for channel 1

Counter 11 - pulse counter for channel 1 or high word of 32Ćbit period measurement

Counter 20 - 16-bit period measurement or low word of 32Ćbit period measurement for channel 2

Counter 21 - pulse counter for channel 2 or high word of 32Ćbit period measurement

Counter 30 - 16-bit period measurement or low word of 32Ćbit period measurement for channel 3

Counter 31 - pulse counter for channel 3 or high word of 32Ćbit period measurement

Readback of Control word 2 or

Reserved

M0

M1

M2

M3

Reserved

Reserved

RD0

RD1

RD2

RD3

System Throughput

Mapping Data into the

Image Table