3–2

Programming Your Pulse Counter Module

Publication 1794ĆUM016B-EN-P - August 2002

PLCĆ2 Family Processor

The 1794 Pulse Counter module is not recommended for use with
PLC-2 family programmable controllers due to the number of digits
needed for high resolution.

Important: The Pulse Counter module functions with reduced

performance in PLC-2 systems. Because the module
does not support BCD and the PLC-2 processor is
limited to values of 4095 (12 bit binary), many values
returned in the BTR file may not provide meaningful
data to the PLC-2 processor.

PLCĆ5 Family Processor

Block transfer instructions with the PLC-5 processor use a control
file and a data file. The block transfer control file contains the data
table section for module location, the address of the block transfer
data file and other related data. The block transfer data file stores
data that you want transferred to the module (when programming a
BTW) or from the module (when programming a BTR).

The programming terminal prompts you to create a control file when
a block transfer instruction is being programmed. A different block
transfer control file is used for the read and write instructions
for
your module.