6–3

Input, Output and Configuration Files for Analog Modules when used with ControlNet

Publication 1794ĆUM016B-EN-P - August 2002

Output data is received by the adapter in the order of the installed
I/O modules. The Output data for Slot 0 is received first, followed
by the Output data for Slot 1, and so on up to slot 7.

The first word of input data sent by the adapter is the Adapter Status
Word. This is followed by the input data from each slot, in the order
of the installed I/O modules. The Input data from Slot 0 is first after
the status word, followed by Input data from Slot 2, and so on up to
slot 7.

Adapter Status

Slot 0 Input Data
Slot 1 Input Data

Slot 7 Input Data

Slot 0 Output Data
Slot 1 Output Data

Slot 7 Output Data

Read Data

Output Data

Network READ

Network WRITE

ControlNet Adapter

Slot 0

I/O Module

Read

Write

Slot 1

I/O Module

Slot 7

I/O Module

...

...

...

...

...

Adapter Input Status Word

The input status word consists of:

I/O module fault bits – 1 status bit for each slot

node address changed – 1 bit (created by PLC–5 controller)

I/O status – 1 bit (created by PLC–5 controller)

15

Bit:

0

1

2

3

4

5

6

7

8

10 through 15

I/O Module Fault Bits

Slot 0

Slot 1

Slot 2

Slot 3

Slot 4

Slot 5

Slot 6

Slot 7

9

I/O State Bit

Not Used

Node Address Changed Bit

Created by PLC-5 controller

The adapter input status word bit descriptions are shown in the
following table.

I/O Structure