Scheduled dataćtransfer, Unscheduled dataćtransfer, Module i/o mapping – Rockwell Automation 1794-IP4 Series B FLEX I/O PULSE COUNTER User Manual User Manual

Page 55

Advertising
background image

6–2

Input, Output and Configuration Files for Analog Modules when used with ControlNet

Publication 1794ĆUM016B-EN-P - August 2002

Scheduled DataĆTransfer

Scheduled data transfer:

is continuous

is asynchronous to the ladder-logic program scan

occurs at the actual rate displayed in the Actual Packet Interval
field on the programming software ControlNet I/O mapping
(monitor) screen

Unscheduled DataĆTransfer

Unscheduled operations include:

unscheduled non-discrete I/O data transfers—through ControlNet
I/O Transfer (CIO) instructions

peer-to-peer messaging—through Message (MSG) instructions

messaging from programming devices

Unscheduled messaging on a ControlNet network is
non-deterministic. Your application and your configuration—number
of nodes, application program, NUT, amount of scheduled bandwidth
used, etc.—determine how much time there is for
unscheduled messaging.

Module I/O Mapping

The I/O map for a module is divided into read words and write
words. Read words consist of input and status words, and write
words consist of output and configuration words. The number of
read words or write words can be 0 or more. The length of each I/O
module’s read words and write words vary in size depending on
module complexity. Each I/O module will support at least 1 input
word or 1 output word. Status and configuration are optional,
depending on the module.

For example, a 16 point discrete input module will have up to 2 read
words and 1 write word.

Module Image

Inputs

Delay

Time

Input Size

Configuration Size

1 or 2 Words

0 or 1 Word

ControlNet Image

Not used

16Ćpoint Discrete Input Module

Delay

Time

Not used

Check the I/O map for each module for the exact mapping.

Advertising