Rockwell Automation 1794-IP4 Series B FLEX I/O PULSE COUNTER User Manual User Manual

Page 28

Advertising
background image

2–12

How to Install Your Pulse Counter Module

Publication 1794ĆUM016B-EN-P - August 2002

Wiring connections for the 1794-IP4 Pulse Counter Module

Channel

Signal

Name

1

Terminal Base Units

1794-TB2, -TB3, -TB3S

Terminal Base Units

1794-TBN, -TBNF

2

Signal

0V dc

(Common) 12/24V dc

Signal

Input

16-bit Period Time Measurement

0

N

0

17

35

0

N

1

18

36

1

1

N

2

19

37

2

N

3

20

38

3

2

N

4

21

39

4

N

5

22

40

5

3

N

6

23

41

6

N

7

24

42

7

32-bit Period Time Measurement

0

D

8

25

43

8

D

9

26

44

9

1

D

10

27

45

10

D

11

28

46

11

2

D

12

29

47

12

D

13

30

48

13

3

D

14

31

49

14

D

15

32

50

15

0V dc

(Common)

Terminals 16 and 33 (1794ĆTB2)

Terminals 16 thru 33 (1794ĆTB3,

ĆTB3S)

Terminals 16 and 33

12/24V dc

Terminals 34 and 51 (1794-TB2)

Terminals 34 thru 51 (1794-TB3

Terminals 34 and 51

1 Any unused signals have to be connected to the associated common.

2 Auxiliary terminal blocks are required when using these terminal base units.

NOTE: If using shielded cable, terminate the shield at the DIN rail (earth ground).

!

ATTENTION: Total current draw through the
terminal base unit is limited to 10A. Separate power
connections to the terminal base unit may be necessary.

Advertising