Connecting wiring for your pulse counter module – Rockwell Automation 1794-IP4 Series B FLEX I/O PULSE COUNTER User Manual User Manual

Page 25

Advertising
background image

2–9

How to Install Your Pulse Counter Module

Publication 1794ĆUM016B-EN-P - August 2002

Wiring to the module is made through the terminal base unit on
which the module mounts.

Compatible terminal base units are:

Module

1794ĆTB3

1794ĆTB3S

1794ĆTBN

1794ĆTBNF

1794-IP4

Yes

Yes

Yes

Yes

0

1

2

3 4 5

6 7

8 9 10 11 12 13 14 15

A

B

C

A

B

C

1794ĆTB3

1794ĆTB3S

35 and 51 = common

0 -15

34-51

16-33

34 and 50 = 24V dc

16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33

34 35 36 37 38 39 40 41 42 43 44 45 46 47 48 49 50 51

16 and 33 = chassis ground

0

1 2

3 4

5 6

7

8

9 10 11 12 13 14 15

18 19 20 21 22 23

33

24 25 26 27 28 29 30 31 32

17

35 36 37 38

47 48 49 50

34

51

16

Labelplaced at top of wiring area.

39 40 41 42 43 44 45 46

40 thru 45 = chassis ground

35 and 51 = common

34 and 50 = 24V dc

16 and 33 = chassis ground

40 thru 45 = chassis ground

Connecting Wiring using a 1794ĆTB3 and ĆTB3S Terminal Base

Units

1. Connect individual input wiring (N+, N–,) or (D+, D–) to

numbered terminals on the 0–15 row (A) as indicated in the table
below.

!

ATTENTION: Do not connect maximum input
voltage simultaneously to all inputs if the module
ambient temperature is expected to exceed 40

o

C.

!

ATTENTION: If the module ambient temperature is
expected to continuously exceed 40

o

C, you must limit

the input voltage using an external resistor on each
input. A 1K

resistor effectively limits a 24V sensor

signal to about 15V at the input. Do not limit the input
to less than 6V.

2. Connect the associated input common to the corresponding

terminal on the 16-33 row (B) for each input as indicated in the
table below.

Connecting Wiring for

Your Pulse Counter

Module