Rockwell Automation 1794-IP4 Series B FLEX I/O PULSE COUNTER User Manual User Manual

Page 50

Advertising
background image

5–5

How Communication Takes Place and I/O Image Table Mapping with the DeviceNet Adapter

Publication 1794ĆUM016B-EN-P - August 2002

Definition

Bit

Word

Read

Word 6

Bits 00-15

(00-17)

Counter 21 - pulse counter or high word of32Ćbit period measurement for channel 2

Read

Word 7

Bits 00-15

(00-17)

Counter 30 - 16-bit period measurement or low word of32Ćbit period measurement for channel 3.

Read

Word 8

Bits 00-15

(00-17)

Counter 31 - pulse counter or high word of32Ćbit period measurement for channel 3

Read

Word 9

Readback of Control Word 2

Word 9

Bit 00

Positive edge - Channel 0 - measurement ready

Bit 01

Positive edge - Channel 1 - measurement ready

Bit 02

Positive edge - Channel 2 - measurement ready

Bit 03

Positive edge - Channel 3 - measurement ready

Bit 04

ResetDone, Channel 0 - a positive edge on this bit indicates counter 01 reset done

Bit 05

ResetDone, Channel 1 - a positive edge on this bit indicates counter 11 reset done

Bit 06

ResetDone, Channel 2 - a positive edge on this bit indicates counter 21 reset done

Bit 07

ResetDone, Channel 3 - a positive edge on this bit indicates counter 31 reset done

Bit 08-15

Reserved for factory use

Read

Word 10

Bits 00-15

(00-17)

Software revision - version code ofsoftware installed

Write

Word 1

Control Word 0 - Control word for setting the function of counter 0.

Word 1

Bits 00

Pulse counting and period time measurement selection for Channel 0 -

0 = pulse counting and period time measurement selected

1 = period time measurement selected

Bits 01

Pulse counting and period time measurement selection for Channel 1 -

0 = pulse counting and period time measurement selected

1 = period time measurement selected

Bits 02

Pulse counting and period time measurement selection for Channel 2 -

0 = pulse counting and period time measurement selected

1 = period time measurement selected

Bits 03

Pulse counting and period time measurement selection for Channel 3 -

0 = pulse counting and period time measurement selected

1 = period time measurement selected

Bits 04-15

(04-17)

Reserved

Advertising