Rockwell Automation 1794-IP4 Series B FLEX I/O PULSE COUNTER User Manual User Manual

Page 61

Advertising
background image

6–8

Input, Output and Configuration Files for Analog Modules when used with ControlNet

Publication 1794ĆUM016B-EN-P - August 2002

Definition

Bit

Configuration

Word

Word1

Bit 00

Clock frequency for period time measurement - Channel 0 -

0 = periodtime measurement with 10MHz internal clock selected

1 = periodtime measurement with 1MHz internal clock selected

Bits 01-03

03

02 01

Number of periods for measurement - Channel 0

0

0

0

1 period

0

0

1

2 periods

0

1

0

4 periods

0

1

1

8 periods

1

0

0

16 periods

1

0

1

32 periods

1

1

0

64 periods

1

1

1

128 periods

Bit 04

Clock frequency for period time measurement - Channel 1 - refer to bit 00.

Bits 05-07

Selection of Number of periods for measurement - Channel 1 - see bits 01-03 above

Bit 08 (10)

Clock frequency for period time measurement - Channel 2 - refer to bit 00.

Bits 09-11

(11-13)

Selection of Number of periods for measurement - Channel 2 - see bits 01-03 above

Bit 12 (14)

Clock frequency for period time measurement - Channel 1 - refer to bit 00.

Bits 13-15

(15-17)

Selection of Number of periods for measurement - Channel 1 - see bits 01-03 above

Word2

Bit 00

Startnew measurementbit- Channel 0 - when set, start new measurement on positive edge

Bit 01

Startnew measurementbit- Channel 1 - when set, start new measurement on positive edge

Bit 02

Startnew measurementbit- Channel 2 - when set, start new measurement on positive edge

Bit 03

Startnew measurementbit- Channel 3 - when set, start new measurement on positive edge

Bit 04

ResetCounter, Channel 0 - a positive edge on this bit resets counter 01

Bit 05

ResetCounter, Channel 1 - a positive edge on this bit resets counter 11

Bit 06

ResetCounter, Channel 2 - a positive edge on this bit resets counter 21

Bit 07

ResetCounter, Channel 3 - a positive edge on this bit resets counter 31

Bit 08-15

(10-17)

Not used

Advertising