Appendix

A

Publication 1794ĆUM016B-EN-P - August 2002

Specifications

Specifications - 4 Channel Pulse Counter Module

(Cat. No. 1794-IP4)

Number of Inputs

4 pulse counter interfaces - 2 inputs each

Counting Frequency

100KHz maximum. Each signal condition must be

stable for at least 2

µ

s to be recognized.

Input Range

Input ON

Input OFF

Maximum 26.4V dc (24V dc +10%)

Minimum 6V dc

Maximum 3V dc

Minimum -26.4V dc

Input Current (typical)

3mA @ 6V dc

9mA @ 12V dc

15mA @ 24V dc

Module Location

Mounts on Cat. No. 1794ĆTB2, TB3, ĆTB3S, and ĆTBN

Terminal Base Units

Isolation Voltage

Tested at 500V dc for 1s

Flexbus Current

5mA @ 5V dc

Power Supply (external)

12-24V dc (+10%)

Current consumption from

external power supply

150mA @ 12V dc

75mA @ 24V dc

Power Dissipation

5W maximum @ 26.4V dc

Thermal Dissipation

Maximum 17.1 BTU/hr @ 26.4V dc

Indicators (field side driven,

logic side indication)

1 green/red power/status indicator

8 yellow status indicators - logic side

Keyswitch Position

1

Dimensions Inches

(Millimeters)

1.8H x 3.7W x 2.1D

(45.7 x 94.0 x 53.3)

Environmental Conditions

Operating Temperature

IEC 60068-2-1 (Test Ad, Operating Cold)

IEC 60068-2-2 (Test Bd, Operating Dry Heat)

IEC 60068-2-14 (Test Nb, Operating Thermal Shock)

32 to 131

°

F (0 to 55

°

C)

Note: Do not connect maximum input voltage

simultaneously to all inputs if the module ambient

temperature is expected to exceed 40

o

C.

Storage Temperature

IEC 60068-2-1 (Test Ab, Unpackaged, Nonoperating

Cold)

IEC 60068-2-2 (Test Bb, Unpackaged, Nonoperating Dry

Heat)

IEC 60068-2-14 (Test Na, Unpackaged, Nonoperating

Thermal Shock)

-40 to 185

°

F (-40 to 85

°

C)

Relative Humidity

IEC 60068-2-30 (Test Db, Unpackaged, Nonoperating

Damp Heat)

5 to 95%, noncondensing

Specifications continued on next page.