6–6

Input, Output and Configuration Files for Analog Modules when used with ControlNet

Publication 1794ĆUM016B-EN-P - August 2002

Pulse Counter Module (1794ĆIP4) Image Table Mapping

Module Image

ControlNet Files

Input File Size

1 to 10 Words

Configuration File Size

0 to 3 Words

Control Word 0 - Sets the measure function

Control Word 2 - sets the start of a new measurement

Control Word 1 - Sets the clock frequency and period multiple

Counter 00 - 16-bit period measurement or low word of 32Ćbit period measurement for channel 0

Code for identification of software version

Counter 01 - pulse counter for channel 0 or high word of 32Ćbit period measurement

Counter 10 - 16-bit period measurement or low word of 32Ćbit period measurement for channel 1

Counter 11 - pulse counter for channel 1 or high word of 32Ćbit period measurement

Counter 20 - 16-bit period measurement or low word of 32Ćbit period measurement for channel 2

Counter 21 - pulse counter for channel 2 or high word of 32Ćbit period measurement

Counter 30 - 16-bit period measurement or low word of 32Ćbit period measurement for channel 3

Counter 31 - pulse counter for channel 3 or high word of 32Ćbit period measurement

Readback of Control word 2 or

Reserved

M0

M1

M2

M3

RD0

RD1

RD2

RD3

Bit/Word Definitions for Block Transfer Read Words

for the

Pulse Counter Module

Input

Word

Bit

Definition

Input

Word 0

Bits 00-15

(00-17)

Store Counter 00 - 16-bit period measurement or low word of 32Ćbit period measurement for channel 0.

1

Bits 00-15

(00-17)

Counter 01 - pulse counter or high word of 32Ćbit period measurement for channel 0

2

Bits 00-15

(00-17)

Counter 10 - 16-bit period measurement or low word of 32Ćbit period measurement for channel 1.

3

Bits 00-15

(00-17)

Counter 11 - pulse counter or high word of 32Ćbit period measurement for channel 1

4

Bits 00-15

(00-17)

Counter 20 - 16-bit period measurement or low word of 32Ćbit period measurement for channel 2.

5

Bits 00-15

(00-17)

Counter 21 - pulse counter or high word of 32Ćbit period measurement for channel 2

6

Bits 00-15

(00-17)

Counter 30 - 16-bit period measurement or low word of 32Ćbit period measurement for channel 3.

Advertising