4–5

Writing Configuration to and Reading Status from Your Module with a Remote I/O Adapter

Publication 1794ĆUM016B-EN-P - August 2002

Bit/Word Definitions for the Block Transfer Write Words for the Pulse

Counter Module

Write

Word

Bit

Definition

Write

Word 0

Control Word 0 - Control word for setting the function of counter 0.

Word 0

Bits 00

Pulse counting and period time measurement selection for Channel 0 -

0 = pulse counting and period time measurement selected

1 = period time measurement selected

Bits 01

Pulse counting and period time measurement selection for Channel 1 -

0 = pulse counting and period time measurement selected

1 = period time measurement selected

Bits 02

Pulse counting and period time measurement selection for Channel 2 -

0 = pulse counting and period time measurement selected

1 = period time measurement selected

Bits 03

Pulse counting and period time measurement selection for Channel 3 -

0 = pulse counting and period time measurement selected

1 = period time measurement selected

Bits 04-15

(04-17)

Reserved

Write

Word 1

Control Word 1 - Control word for setting period measurement

Word 1

Bit 00

Clock frequency for period time measurement - Channel 0 -

0 = period time measurement with 10MHz internal clock selected

1 = period time measurement with 1MHz internal clock selected

Bits 01-03

03

02 01

Number of periods for measurement - Channel 0

0

0

0

1 period

0

0

1

2 periods

0

1

0

4 periods

0

1

1

8 periods

1

0

0

16 periods

1

0

1

32 periods

1

1

0

64 periods

1

1

1

128 periods

Bit 04

Clock frequency for period time measurement - Channel 1 - refer to bit 00.

Bits 05-07

Selection of Number of periods for measurement - Channel 1 - see bits 01-03 above

Bit 08 (10)

Clock frequency for period time measurement - Channel 2 - refer to bit 00.

Bits 09-11

(11-13)

Selection of Number of periods for measurement - Channel 2 - see bits 01-03 above

Bit 12 (14)

Clock frequency for period time measurement - Channel 1 - refer to bit 00.

Bits 13-15

(15-17)

Selection of Number of periods for measurement - Channel 1 - see bits 01-03 above

Write

Word 2

Control Word 2 - starts new measurement

Word 2

Bit 00

Start new measurement bit - Channel 0 - when set, start new measurement on positive edge

Bit 01

Start new measurement bit - Channel 1 - when set, start new measurement on positive edge

Bit 02

Start new measurement bit - Channel 2 - when set, start new measurement on positive edge

Bit 03

Start new measurement bit - Channel 3 - when set, start new measurement on positive edge

Advertising