3–4

Programming Your Pulse Counter Module

Publication 1794ĆUM016B-EN-P - August 2002

Figure 3.1

SLC Programming for the 1794ĆIP4 Pulse Counter Module

PowerUp Bit

0000

Program Action

S2:1

15

BTR_CONTROL

COP

COPY FILE
SOURCE
DEST

#B3:100

#M0:1.100

LENGTH

3

BTW_CONTROL

COP

COPY FILE
SOURCE
DEST

#B3:110

#M0:1.200

LENGTH

3

COP

COPY FILE
SOURCE
DEST

#M1:1.100

#B3:0

LENGTH

4

0001

BTR PENDING

B3:5

0

This rung configures the block transfer operation

type, length, and RIO address at powerĆup. Bit

B3:100/7 must be set to 1 to indicate a BTRand

bit B3:110/7 must be 0 to indicate a BTW.

U

BTR DONE BIT

B3:0

13

CHECK BTR STATUS

B3:5

1

BTR ERROR BIT

B3:0

12

0002

B3:5

1

COP

COPY FILE
SOURCE
DEST

#M1:1.200

#B3:10

LENGTH

4

0003

BTW PENDING

B3:15

0

CHECK BTW STATUS

B3:15

1

BTRstatus is copied to the B3:0 area when a BTR

is in progress.

Unlatch the bit that continues to check the BTRstatus.

BTW status is copied to the B3:100 area when a

BTW is in progress.

To next page.

0004

U

BTW DONE BIT

B3:10

13

BTW ERROR BIT

B3:10

12

B3:15

1

Unlatch the bit that continues to check the BTW status.

CHECK BTW STATUS

CHECK BTR STATUS

The 1794ĆIP4 module is located in remote I/O rack 1, group 0, slot 0. The 1747ĆSN scanner module is located in slot 1 of the SLC chassis. This program enables

1 BTW to configure the 1794ĆIP4 module at powerĆup. Thereafter, BTrs will be performed continuously to obtain data from the 1794ĆIP4 module.

TRIGGERFORBTW

N7:20

0