Installation precautions, Environment and enclosure information, European union directive – Rockwell Automation 6181F_P Series E Integrated Display Computers User Manual User Manual

Page 18

Advertising
background image

18

Rockwell Automation Publication 6181P-UM002D-EN-P - February 2014

Chapter 2

Installation

Installation Precautions

Read and follow these precautions before installing the computer.

Environment and Enclosure Information

European Union Directive

This computer meets the European Union Directive requirements when installed
within the European Union or EEA regions and have the CE mark. A copy of the
declaration of the conformity is available at

http://www.rockwellautomation/

certification

.

ATTENTION: This equipment is intended for use in a Pollution Degree 2 industrial
environment, in overvoltage Category II applications (as defined in IEC 60664-1),
at altitudes up to 2000 m (6561 ft) without derating.

This equipment is considered Group 1, Class A industrial equipment according to
IEC/CISPR 11. Without appropriate precautions, there can be potential difficulties
ensuring electromagnetic compatibility in other environments due to conducted as
well as radiated disturbance.

This equipment is supplied as an open type equipment. The interior of the
enclosure must be accessible only by the use of a tool. UL Listed equipment does
not need to be mounted inside another enclosure.

In addition to this publication, see the following:

Industrial Automation Wiring and Grounding Guidelines, publication

1770-4.1

,

for additional installation requirements

NEMA Standard 250 and IEC 60529, as applicable, for explanations of the

degrees of protection provided by enclosures

ATTENTION: This computer is intended to operate in an industrial or control
room environment, which uses some form of power isolation from the public
low–voltage mains. Some computer configurations cannot comply with the
EN 61000-3-2 Harmonic Emissions standard as specified by the EMC Directive of
the European Union. Obtain permission from the local power authority before
connecting any computer configuration that draws more than 75 W of AC power
directly from the public mains.

To comply with EN 55024, the Ethernet port LAN cable must be only used indoors.
All other I/O cables must be less than 3 m (9.84 ft) and only used indoors.