DataSite and Logix Integration Chapter 3

Configure ControlLogix Communication

This procedure assumes that communication to the Logix controller is using the Ethernet port. It
also assumes that your 1756-ENBT Ethernet/IP module has already been configured with an IP
address of 192.168.10.90.

For additional information, refer to the ControlLogix Controllers User Manual, publication

1756-UM051

.

Follow these steps to configure ControlLogix communication.

1. Open the RSLinx Classic software, then choose Configure Drivers... from the

Communications menu.

The Configure Drivers
Window opens.

2. Select Ethernet devices

from the pull-down list.

3. Click the Add New

button.

4. Accept the default driver

name, AB_ETH-1, or
change the name and
click OK.