Before you begin, Appendix b, Datasite to factorytalk view se master – Rockwell Automation 1758 DataSite Accelerator Toolkit User Manual
Page 95: Appendix
 
95
Publication IASIMP-QS008A-EN-P - March 2009
95
Appendix
B
DataSite to FactoryTalk View SE Master
This appendix shows how to configure an industrial computer running FactoryTalk View SE 
software to communicate with a DataSite unit using Modbus TCP/IP communication. This setup 
requires KEPServerEnterprise software V4.0 to configure the communication driver.
This configuration is good for small applications that require data logging capabilities but don't 
require a ControlLogix controller to poll multiple DataSite units. Refer to 
on how to configure a PanelView Plus terminal running Factory Talk View ME software to 
communicate with the DataSite using Modbus serial communication.
Before You Begin
•
Download KEPServer Enterprise software V4.0.
•
Connect the DataSite unit to an industrial computer running FactoryTalk View Site Edition 
(SE) software. 
•
Radios are optional.
6181P Industrial Computer Running
FactoryTalk View SE
Radio
Et
he
rn
et
Remote Location
Radio
Et
he
rn
et
Host Location
2711
P-
C
B
L-
EX
04
Cr
oss
over
Cable
2711P-
CBL-
EX04
Cr
os
so
ve
r Ca
bl
e
TIP
Radios are optional. If your application does not require radios, simply replace the radios 
with an Ethernet crossover cable connecting the DataSite to the industrial computer.