Publication IASIMP-QS008A-EN-P - March 2009

Appendix A DataSite to FactoryTalk View ME Master

6. Wait for the application to the

load and verify that
DataSite_ME_Modbus_Serial.
mer appears under Current
application.

7. Press Run Application [F2].

The application builds and displays
a DataSite screen on the PanelView
Plus terminal.

8. Press Process Variables &

Compressibility.

Verify the process variables match
the numbers simulated using DS
FloConfig:

Static Pressure = 800
Temperature = 80
Differential Pressure = 70

9. Return to the main screen and press the other two blue buttons to view accumulated flow

data.

The flow data displayed is for Meter Run 0 (MR0). You can easily add other meter runs by adding
the corresponding Modbus registers in the KEPServerEnterprise (.pfe) file. You must then
duplicate the ME screens and change the tag names to match their corresponding tag name.

Configuration and validation of the DataSite to ME Master configuration is now complete.

IMPORTANT

If the PanelView Plus terminal displays asterisks instead of data, then you need to select a different COM
port for the Serial DF1 driver. Skip to page

91

for instructions on how to change the COM port.