DataSite to FactoryTalk View ME Master

This appendix describes how to configure a PanelView Plus 600 terminal to communicate with
the DataSite using Modbus serial communication. This setup requires KEPServerEnterprise V4.0 to
configure drivers between the DataSite unit and the PanelView Plus terminal running FactoryTalk
View ME.

Use this setup for smaller applications that don't require a ControlLogix controller to poll multiple
DataSite units. Refer to Appendix B for instructions on how to configure a Factory Talk View SE
master to communicate with the DataSite via Modbus TCP/IP communication that don’t require a
controller but do require data logging parameters to an excel file.

Before You Begin

Download KEPServer Enterprise V4.0.

Wire the DataSite unit to the PanelView Plus 600 terminal using the 2711-NC13 serial cable.

Apply Power to the DataSite unit and PanelView Plus 600 terminal.

What You Need

Personal computer

Hardware:

DataSite unit
PanelView Plus 600 terminal

2711-NC13 Serial Cable

Ethernet Crossover Cable

Programming Computer

Running

FactoryTalk View ME

2711P PanelView Plus 600 Terminal

with Built-in Ethernet Port

2711P-CBL-EX04