Publication GMC-RM001A-EN-P — July 2001

A-6

Noise Control Supplement

Method

Both 24V dc commons were grounded to the panel (refer to
Figure A.4).

500mm parallel wire runs were set up at varying distances apart
(separation) and different heights above the panel (wire to panel).

Peak voltages were measured on the victim wire referenced to the
panel.

Figure A.4
Wire segregation test set-up

Results

The results of the segregation testing is shown in the table below.

Wire to

panel

Victim

wire

Source

wire

Steel wall

Separation

Plated steel panel

Source and Victim
Separation:

Wire to Panel Separation:

3.0 mm (0.1 in.)

3.0 mm (0.1 in.)

3.0 mm (0.1 in.)

40 mm (1.6 in.)

40 mm (1.6 in.)

40 mm (1.6 in.)

24V dc Resistive
Load

24V dc Contactor 240V ac

Contactor

24V dc Resistive
Load

24V dc Contactor 240V ac

Contactor

3mm (0.1in)

500mV

10V

10V

500mV

20V

20V

25mm (1in)

100mV

500mV

200mV

100mV

5V

2V

50mm (2in)

100mV

200mV

200mV

100mV

2V

2V

100mm (4in)

100mV

200mV

200mV

100mV

1V

1V

200mm (8in)

100mV

100mV

100mV

100mV

200mV

200mV

3mm + Steel wall

100mV

500mV

100mV

100mV

500mV

500mV

25mm + Steel wall

100mV

100mV

100mV

100mV

500mV

200mV