Transformers, Transformers -3 – Rockwell Automation System Design for the Control of Electrical Noise User Manual

Page 61

Advertising
background image

Publication GMC-RM001A-EN-P — July 2001

Power Distribution

7-3

Transformers

An isolation transformer is frequently assumed to give good noise
isolation. In fact, this only applies if the transformer is equipped with
one or more electrostatic (ES) shields, as shown in the figure below.

Figure 7.3
Electrostatically shielded transformer

This technique is very effective, though generally EMC filters are
required to meet European regulation standards. Observe the
following guidelines when installing transformers.

Install the transformer to the same panel as the rest of your system
(or HF bond from panel-to-panel).

Treat wiring between transformer and drive as very-dirty (provide
shielding as required).

Bond shield, if used, with braid directly to the panel. The
transformer mounting bolts are useful for this purpose.

Segregate input and output wiring as far as possible.

Primary

Secondary

Ground Plane

Frame bonded to
ground plane

Shield(s) bonded to

ground plane

IMPORTANT

The effectiveness of the transformer depends solely
on the HF bond between shields and drive chassis.

Advertising