Single 24v dc switch-mode psu zoning example – Rockwell Automation System Design for the Control of Electrical Noise User Manual

Page 64

Advertising
background image

Publication GMC-RM001A-EN-P — July 2001

7-6

Power Distribution

Single 24V dc Switch-Mode PSU Zoning Example

In the figure below, a 24V dc supply is mounted in the dirty zone,
because it may create noise. But, the noise is reduced by filtering
before the output enters the clean zone.

Figure 7.5
24V dc power distribution with single PSU

Grounded, de-coupling capacitors are used at each clean load (refer
to the chapter High Frequency (HF) Bonding for details). Provided the
system is correctly bonded, the multiple common/ground connections
are not a problem. The copper becomes a backup conductor. No
segregation or filtering is necessary for the load in the dirty zone.

24V dc PSU

AC

Filter

+24V

24V com

Dirty Zone

Clean Zone

Dirty Load

Clean Load

Segregation

De-coupling

capacitor

Filter