Publication GMC-RM001A-EN-P — July 2001

Power Distribution

7-13

Long Power Cable Runs

The 24V dc lines entering or leaving panels that cannot be bonded
together by flat strips (no longer than 10 times the width) should have
filters at the point of entry.

Figure 7.12
Long cable runs between panels

Note: If heavy circulating currents at power frequency are likely, the

floating filter technique or separate, local PSU’s, may be safer to
use.

+24V

24V com

Panel A