Figure a.9 grounded common – Rockwell Automation System Design for the Control of Electrical Noise User Manual

Page 112

Advertising
background image

Publication GMC-RM001A-EN-P — July 2001

A-10

Noise Control Supplement

In Figure A.8, 6.0V common-mode noise spikes are seen at the +24V
dc terminal relative to ground.

Figure A.8
20A, 24V dc PSU (ungrounded, no-load)

In Figure A.9 the noise amplitude is reduced to around 500mV pk,
adequate for general-purpose, dirty loads.

Figure A.9
Grounded common

6.0V pk

Sitop Power 20 with 3 phase input - no load

Common Mode Noise +24 Volts to Backplane

10V

8

6

4

2

0

-2

-4

-6

-8

-10V

ms

-1

0

1

2

3

4

5

6

7

8

9

500 mV pk

Sitop Power 20 with 3 phase input - Common grounded

Common Mode Noise +24 Volts to Backplane

10V

8

6

4

2

0

-2

-4

-6

-8

-10V

-1

0

1

2

3

4

5

6

7

8

9 µs