E-field sniffing method, E-field sniffing method -3 – Rockwell Automation System Design for the Control of Electrical Noise User Manual

Page 93

Advertising
background image

Publication GMC-RM001A-EN-P — July 2001

Measuring Noise Reduction Effectiveness

11-3

E-Field Sniffing Method

The E-field is the electric field capacitively coupled to the probe. To
use the E-field sniffing method:

1. Attach a 150 mm (6 in.) length of stiff insulated wire to the probe

tip to form an antenna.

2. Remove the probe ground clip or attach it to the scope cable to

ensure it does not contact anything.

3. Hold the wire parallel to and touching potential victim wiring and

measure the voltage spikes.

Note: The signal observed is with respect to the scope ground. Check

the method by holding the wire against the panel. There should
be little noise observed (refer to the section Ground Loops for
more information).

Figure 11.1
Simple E-field probe

Advertising