Performance test set-up, Test results, Performance test set-up -4 test results -4 – Rockwell Automation System Design for the Control of Electrical Noise User Manual

Page 50

Advertising
background image

Publication GMC-RM001A-EN-P — July 2001

5-4

Filtering Noise

Performance Test Set-up

The filter performance test included the following components:

24V dc power supply with grounded common filter

Filter mounted to DIN rail

Relay coil to simulate an inductive load

100M Hz sampling digital storage oscilloscope

Test components mounted on a large zinc plated steel panel

Figure 5.4
Filter test block diagram

Test Results

Filter

Measurement point

Filter under

test

24V dc

PSU

Ground Plane - conductive metal panel

Suppression

Switched load

1 m (39 in.) wire

This test condition:

With
No filter:

With
Capacitor only:

With Capacitor
and ferrite sleeve:

No Suppression

200V pk

5.5V pk

674mV pk

R/C
Across coil
100R/0.1uF

5.5V pk

932mV pk

168mV pk

R/C
Across switch
100R/0.1uF

2.5V pk

103mV pk

70mV pk

Transorb
Across coil

14.9V pk

1.8V pk

658mV pk

Transorb
Across switch

8.1V pk

1.4V pk

1.2V pk

Diode

12V pk

63mV pk

63mV pk

Note: Voltages were measured between the measurement point and the ground plane (refer to Figure 5.4 for

exact location.

Advertising