Publication GMC-RM001A-EN-P — July 2001

Shielding Wires, Cables, and Components

4-5

In Figure 4.5 the cable is locally shielded to cross another zone. Each
shield is grounded at each boundary and the cable is run close to the
panel. The outer shield A is a thick walled steel conduit.

Figure 4.5
Very-dirty cable in clean zone

The principle works both ways. In Figure 4.6 the clean cable passes
through a very-dirty zone.

Figure 4.6
Clean cable in very-dirty zone

A

Minimum 150 mm (6.0 in.) segregation

Dirty Zone

Dirty Zone

Dirty Zone

Very-Dirty Zone

Very-Dirty Zone

EMC

filter to drive

Motor power

cable

24V dc I/O

cable

Clean

Zone

A

Dirty Zone

Dirty Zone

Dirty Zone

Clean Zone

Clean Zone

24V dc I/O

cable

Very-Dirty

Zone

Analog device

cable

Encoder

cable

Minimum 150 mm (6.0 in.) segregation