Dedicated power supply, Detection device mounting – Rockwell Automation System Design for the Control of Electrical Noise User Manual

Page 80

Advertising
background image

Publication GMC-RM001A-EN-P — July 2001

9-4

High Speed Registration Inputs

Dedicated Power Supply

In the figure below, the registration input has a dedicated linear
power supply.

Figure 9.3
Dedicated registration power supply

Detection Device Mounting

A line driver or push-pull output is preferred, but not widely available
except in specialized photoelectric sensors for mark detection.

Ideally, the device body should be insulated from the machine
structure and connected to the cable shield.

If the sensor cannot be insulated, ground the shield to the structure or
sensor mounting.

+

24V dc Linear PSU

Segregation

Filter

Dirty Zone

Clean Zone

Keep short or shield
(ground shield on both ends)

Insulated mounting (preferred)

Registration Input

Detector

com

AC

Advertising