Publication GMC-RM001A-EN-P — July 2001

Noise Control Supplement

A-7

Figure A.5
Wire segregation test results

Figure A.6
Wire segregation test panel

Conclusions

The following statements summarize the results of the testing.

150 mm (6 in.) is a reasonable minimum separation required even
for short runs.

A well grounded steel dividing wall is as good or better than 200
mm (8 in.) of separation.

Very noisy or very sensitive wires are best placed close to the
backplate if possible (this is good EMC practice).

Wire Segregation Test

500 mm run, unsuppressed relay coil

0.01

0.1

1

10

100

0

25

50

100

200

Horizontal Separation mm

Victim Noise Vp

k

40 mm

3 mm