Routing system wires and cables between panels, Routing system wires and cables between panels -8 – Rockwell Automation System Design for the Control of Electrical Noise User Manual

Page 40

Advertising
background image

Publication GMC-RM001A-EN-P — July 2001

3-8

Segregating Sources and Victims

Minimizing Loops

Wires that form a loop make an efficient antennae. Run feed and
return wires together rather than allowing a loop to form. Twisting the
pair together further reduces the antennae effects. Refer to the figure
below for an illustration.

Note: This applies to potential victim wiring too. Antennae work

equally well in both receive and transmit modes.

Figure 3.4
Avoiding loops in wiring designs

Routing System Wires and
Cables Between Panels

Follow the same segregation guidelines when wiring between panels
and machine devices.

Maintain clean, dirty, and very-dirty noise zones.

Always use separate, grounded, metal wireways.

Not Recommended

Good Solution

Better Solution

Switch

Switch

Switch