Rockwell Automation System Design for the Control of Electrical Noise User Manual

Page 60

Advertising
background image

Publication GMC-RM001A-EN-P — July 2001

7-2

Power Distribution

Commercial filters are tested, as shown in the figure below, with all
devices properly bonded to a conductive metal ground plane. Proper
bonding techniques are essential to achieve the published attenuation
figures. Refer to the chapter High Frequency (HF) Bonding for more
information on bonding.

Figure 7.1
Filter test set-up

In the example below, noise couples directly from the filter input
wires to the filter output wires and bypasses the filter. You can avoid
this common mistake by shielding and/or segregating the cables and
reducing the cable length.

Figure 7.2
Improper line filter installation example

IMPORTANT

The effectiveness of the line filter depends solely on
the HF bond between filter case and drive chassis.

Measuring
Instrument

Signal

Generator

Filter under test

Ground Plane - conductive metal panel

AC Line

Close spacing

Unshielded cable

Long distance

PWM Drive

AC

Line Filter

ATTENTION

!

To avoid personal injury and/or damage to
equipment, ensure AC line filter capacitors are
properly connected to safety (PE) ground.

Advertising