A–8

RSView32 Runtime User’s Guide

[OutOfAlarm]Indicates that the tag has gone out

of

or [Out]

alarm.

[InAndOut

Indicates that an alarm has occurred,

OfAlarm]

but the tag is again immediately out

of

or

alarm, such as a digital change–of–

[InAndOut] state alarm.

[TagType]

The type of tag, which must be one of:

[/A]

Analog

[/D]

Digital

If you don’t specify either /A or /D, the alarm is
assumed to be analog.

[/VTagValue]

A floating–point value associated with the alarm
event. If the floating–point value is not specified,
the tag value is 0.0.

If the name of an alarm event is the name of a tag
in the tag database, the value specified by this
parameter will not update the tag’s value in the
value table.

[/SSeverity]

The alarm severity. The severity is an integer from 1
to 8. Alarm severity can be specified only for alarm
events of type IntoAlarm, or InAndOutOfAlarm.
If a value is not specified, the alarm severity is 1.