Rockwell Automation RSView32 Runtime Users Guide User Manual
Page 39
A–8
RSView32 Runtime User’s Guide
[OutOfAlarm]Indicates that the tag has gone out
of
or [Out]
alarm.
[InAndOut
Indicates that an alarm has occurred,
OfAlarm]
but the tag is again immediately out
of
or
alarm, such as a digital change–of–
[InAndOut] state alarm.
[TagType]
The type of tag, which must be one of:
[/A]
Analog
[/D]
Digital
If you don’t specify either /A or /D, the alarm is
assumed to be analog.
[/VTagValue]
A floating–point value associated with the alarm
event. If the floating–point value is not specified,
the tag value is 0.0.
If the name of an alarm event is the name of a tag
in the tag database, the value specified by this
parameter will not update the tag’s value in the
value table.
[/SSeverity]
The alarm severity. The severity is an integer from 1
to 8. Alarm severity can be specified only for alarm
events of type IntoAlarm, or InAndOutOfAlarm.
If a value is not specified, the alarm severity is 1.