RSView32 commands

A–43

To log comments, the Remarks category must be selected in the
Activity Log Setup editor.

RTDataServer

Off

RTDataServerOff

Stops running the RSView32 real-time data server.

RTDataServerOn

RTDataServerOn [/Quiet] [/NetDDE]

The RSView32 OPC or DDE server is also known as the real-time
data server. This command runs the RSView32 real-time data server,
allowing OPC and DDE client applications to read (but not write) tag
values.

To enable writes, use the RTDataWriteEnable command.

[/Quiet]

Makes RSView32 use the current Remote Users
accessibility setting in the Windows Registry. Without
this parameter or if the setting is not configured
correctly, RSView32 displays a dialog box that allows
you to specify the setting when you issue the
command.

[/NetDDE]

Enables RSView32 as a NetDDE server to remote
DDE clients. If the real-time data server is already
running, this parameter is ignored.

RTDataWrite

Disable

RTDataWriteDisable [/Quiet] [/NetDDE]

Disables writes by external Windows applications running OPC or
DDE, so these applications cannot change tag values in RSView32.

The RSView32 OPC or DDE server is also known as the real-time
data server. If the RSView32 real-time data server is not running—
that is, if the RTDataServerOn command has not been run—